  1. <?xml version="1.0" encoding="utf-16"?>
  2. <Interlock xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns:xsd="http://www.w3.org/2001/XMLSchema">
  3. <Action do="DO_Pumping_valve_" value="true" tip="Open pump valve" tip.zh-CN="打开抽气阀门" tip.en-US="">
  4. <Limit di="DI_Lever1_pump_running" value="true" tip="pump not running" tip.zh-CN="泵没有打开" tip.en-US="" />
  5. <Limit di="DI_Lever1_pump_overload" value="false" tip="pump overload alarmed" tip.zh-CN="泵过载报警" tip.en-US="" />
  6. <Limit di="DI_Chamber_vent_valve_state_fb" value="false" tip="vent valve is opened" tip.zh-CN="充气阀门打开" tip.en-US="" />
  7. <Limit di="LogicPumpN2PressureAlarm" value="false" tip="n2 pressure alarm" tip.zh-CN="干泵氮气不足" tip.en-US="" />
  8. <Limit di="LogicPumpWaterFlowAlarm" value="false" tip="water flow alarmed" tip.zh-CN="干泵冷却水流量报警" tip.en-US="" />
  9. <Limit di="DI_Lever1_pump_stop_bt" value="false" tip="stop button pushed" tip.zh-CN="干泵停止按钮被按下" tip.en-US="" />
  10. <Limit di="DI_Lever1_pump_temp_alarm" value="false" tip="temperature high alarm" tip.zh-CN="干泵温度过高报警" tip.en-US="" />
  11. </Action>
  12. <Action do="DO_RF_on_off" value="true" tip="rf power on" tip.zh-CN="打开射频开关" tip.en-US="">
  13. <Limit di="DI_RF_hardware_interlock" value="true" tip="RF hardware interlock not satisfied" tip.zh-CN="射频硬件互锁条件不满足" tip.en-US="" />
  14. <Limit di="DI_Chamber_door_sw" value="true" tip="chamber door is opened" tip.zh-CN="腔体门打开" tip.en-US="" />
  15. <Limit di="DI_Lever1_pump_running" value="true" tip="pump not running" tip.zh-CN="泵没有打开" tip.en-US="" />
  16. <Limit di="DI_Chamber_vent_valve_state_fb" value="false" tip="vent valve is opened" tip.zh-CN="充气阀门打开" tip.en-US="" />
  17. <Limit di="DI_Pumping_valve_state_fb" value="true" tip="pumping valve not open" tip.zh-CN="抽气阀门没打开" tip.en-US="" />
  18. <Limit di="DI_Lever1_pump_overload" value="false" tip="pump overload alarmed" tip.zh-CN="泵过载报警" tip.en-US="" />
  19. <Limit di="DI_RF_over_temp_" value="false" tip="rf temperature high alarmed" tip.zh-CN="射频温度过高报警" tip.en-US="" />
  20. </Action>
  21. <Action do="DO_MFC1_valve__" value="true" tip="open mfc1 valve" tip.zh-CN="打开气路阀门" tip.en-US="">
  22. <Limit di="DI_Lever1_pump_running" value="true" tip="pump not running" tip.zh-CN="泵没有打开" tip.en-US="" />
  23. <Limit di="DI_Lever1_pump_overload" value="false" tip="pump overload alarmed" tip.zh-CN="泵过载报警" tip.en-US="" />
  24. <Limit di="DI_Chamber_vent_valve_state_fb" value="false" tip="vent valve is opened" tip.zh-CN="充气阀门打开" tip.en-US="" />
  25. </Action>
  26. <Action do="DO_MFC2_valve" value="true" tip="open mfc2 valve" tip.zh-CN="打开气路阀门" tip.en-US="">
  27. <Limit di="DI_Lever1_pump_running" value="true" tip="pump not running" tip.zh-CN="泵没有打开" tip.en-US="" />
  28. <Limit di="DI_Lever1_pump_overload" value="false" tip="pump overload alarmed" tip.zh-CN="泵过载报警" tip.en-US="" />
  29. <Limit di="DI_Chamber_vent_valve_state_fb" value="false" tip="vent valve is opened" tip.zh-CN="充气阀门打开" tip.en-US="" />
  30. </Action>
  31. <Action do="DO_Chamber_purge_valve" value="false" tip="" tip.zh-CN="" tip.en-US="">
  32. </Action>
  33. <Action do="DO_Process_gas_final_valve" value="false" tip="" tip.zh-CN="" tip.en-US="">
  34. </Action>
  35. <Action do="DO_Chamber_vent_valve" value="true" tip="open vent valve" tip.zh-CN="打开充气阀门" tip.en-US="">
  36. <Limit di="DI_Pumping_valve_state_fb" value="false" tip="Pumping valve is opened" tip.zh-CN="抽气阀门打开" tip.en-US="" />
  37. </Action>
  38. </Interlock>