							- using System;
 
- using System.Xml;
 
- using Aitex.Core.RT.Device;
 
- using Aitex.Core.RT.Event;
 
- using Aitex.Core.RT.IOCore;
 
- using Aitex.Core.Util;
 
- using Aitex.Core.RT.Log;
 
- using MECF.Framework.Common.Equipment;
 
- namespace Venus_RT.Devices.IODevices
 
- {
 
-     /// <summary>
 
-     /// 心跳包机制
 
-     ///
 
-     /// 功能:
 
-     /// 1.C#送出给PLC,如果PLC检测到C#心跳信号停止,则判定C#程序运行异常,从而触发安全逻辑动作。
 
-     /// 2.C#检测PLC返回的心跳包信号,如果检测到PLC心跳信号停止,则判定PLC程序运行异常,从而进行报警处理。
 
-     /// </summary>
 
-     public class IoHeartbeat : BaseDevice, IDevice
 
-     {
 
-         private readonly int PLC_Heart_Beat_Timeout_ms = 1000 * 120;
 
-         private readonly AIAccessor _ai;
 
-         private readonly AOAccessor _ao;
 
-         private readonly DeviceTimer _updateTimer = new DeviceTimer();  //更新 AO信号 给PLC
 
-         private readonly int MAX = 0x7FFF;
 
-         private float _prevAiValue;
 
-         private readonly DeviceTimer _connectTimer = new DeviceTimer();
 
-         private readonly R_TRIG _trigConnectionLost = new R_TRIG();
 
-         // --------------------------Constructor-----------------------
 
-         // 
 
-         public IoHeartbeat(string module, XmlElement node, string ioModule = "")
 
-         {
 
-             base.Module = module;
 
-             base.Name = node.GetAttribute("id");
 
-             base.Display = node.GetAttribute("display");
 
-             base.DeviceID = node.GetAttribute("schematicId");
 
-             _ai = ParseAiNode("ai", node, ioModule);
 
-             _ao = ParseAoNode("ao", node, ioModule);
 
-         }
 
-         public bool Initialize()
 
-         {
 
-             _updateTimer.Start(500);
 
-             _connectTimer.Start(PLC_Heart_Beat_Timeout_ms);
 
-             return true;
 
-         }
 
-         public void Monitor()
 
-         {
 
-             if (Math.Abs(_prevAiValue - _GetRealFloat(_ai)) > 0.01)
 
-             {
 
-                 _connectTimer.Start(PLC_Heart_Beat_Timeout_ms);
 
-             }
 
-             _trigConnectionLost.CLK = _connectTimer.IsTimeout();
 
-             if (_trigConnectionLost.Q)
 
-             {
 
-                 LOG.Write(eEvent.ERR_PLC_HEARTBEAT_FAIL, ModuleHelper.Converter(Module), Display);
 
-             }
 
-             _prevAiValue = _GetRealFloat(_ai);
 
-             //如果计时到达,则翻转心跳信号
 
-             if (_updateTimer.IsTimeout())
 
-             {
 
-                 float beat_val = _GetRealFloat(_ao);
 
-                 beat_val++;
 
-                 if (beat_val >= MAX)
 
-                 {
 
-                     beat_val = 0;
 
-                 }
 
-                 _SetRealFloat(_ao, beat_val);
 
-                 _updateTimer.Start(3000);       //500 ms
 
-             }
 
-         }
 
-         public void Terminate() {  }
 
-         public void Reset()
 
-         {
 
-             _connectTimer.Start(PLC_Heart_Beat_Timeout_ms);
 
-             _trigConnectionLost.RST = true;
 
-         }
 
-     }
 
- }
 
 
  |